Product
1 : Use
It is used in the fireproof and fire retardation protection of all kinds cable with different voltage grade. Mainly used in fireproof protection of electricity plant, transformer station,petroleum, chemical, construction and communication etc..
2 : Technical Characteristics
AB-G60 cable fire retardant coating has excellent heat insulation properties, strong adhesion, good flexility and resistance to water, oil, salt water and weather.
3 : Technical Indexes
Item
|
Index
|
|
Flame retardant property(m)
|
Charring height 0.46
|
|
Appearance
|
No caking, white think liquid
|
|
Fineness(µm)
|
≤90
|
|
Drying Time
|
Surface/h
|
≤2
|
Whole/h
|
≤8
|
|
Oil resistance/d
|
Soak for 7 days, no shrinking or drops
|
|
Salt resistance /d
|
Soak for 3 days, no shrinking or drops
|
|
Resistance to wet heat/d
|
Soak for 7 days, no shrinking or drops
|
|
Resistance to cold and heat periodicity/time
|
After 15 circulation,no bubble or drops
|
|
Bending resistance
|
No shrinking or drops
|
4 : Constructional parameters
Use level of coating/g/m2
|
300-330
|
Thickness of coating film mm
|
0.20-0.22
|
Painting alternation/h
|
≥10
|
Coating times
|
5
|
Coating method
|
Brush coating or spray coating
|
Thinner
|
xylene or 200# solvent oil
|
Diluted amount
|
0-3%
|
5 : Packaging and storage
Packed in metal pail, 20l per pail, stored in draughty and dry place. , quality guarantee period: 1 years.